Power Utilization within a Colocation Environment

The most common rack's circuit arrangement is known as A/B redundant (aka: Primary + redundant circuit).


The most common rack's circuit arrangement is known as A/B redundant (aka: Primary + redundant circuit). It enables a total permissible continuous power consumption of 4,992watts in a single cabinet; at a combined 23A across both circuits (11.7A on one 208V/30A circuit & 11.8A on the other 208V/30A circuit).

Let's talk about a few more of the details:

Headroom

In A/B redundant mode, either circuit must have sufficient headroom to support a full electrical load in the event one circuit fails...hence why neither 30A circuit should ever exceed 12A of continuous consumption.

Bursting & Continuous Load

There is a built-in buffer between bursty loads and maximum continuous rated loads: per the National Electrical Code (NEC), the maximum permitted continuous rated circuit capacity on a 30 amp nominal rated circuit is 24 amps (80%). That 80% requirement inherently buys you a 20% buffer between typically higher burst loads, and often lower continuous loads. This helps lower the risk of a circuit popping during bursty load times, but circuit breakers can and have been known to pop inside of the 24A-30A buffer. Such pops are exceedingly rare, but do occur.

The Dangers

The NEC's mandatory 20% buffer cannot be encroached upon for continuous/ongoing loads: the good colocation facilities frequently measures/audits usage; if you exceed more than 40% consumption of either circuit in an A/B redundant configuration, you would lose all reasonably expected benefits of electrical circuit fault-tolerance. As a failure of either circuit would inherently shift 100% of electrical loads to a single circuit...which too would pop; powering off the entire cabinet (if this occurs after-hours, colo personel would need to be onsite and remedy). Exceeding more than 40% per circuit in A/B redundant mode also means you'd can often be billed at the colos primary+primary circuit rate. There also could be some heating concerns if in a cabinet as greater than 5KW/cabinet of consumption can exceed the rated per cabinet cooling capacity.

Similar posts

Get notified on new marketing insights

Be the first to know about new B2B SaaS Marketing insights to build or refine your marketing function with the tools and knowledge of today’s industry.